STRUCTURAL CALCULATIONS
FOR
Example 6 - Wind
Example 11 - Seismic
2000 IBC Handbook - Structural Provisions
Company
JOB TITLE
Address
City, State
Phone
other
JOB NO.
Example 6 & 11 - 2000 IBC
SHEET NO.
CALCULATED BY
DATE
CHECKED BY
DATE
[Link]
Code Search
I.
Code:
II.
Occupancy:
International Building Code 2000
Occupancy Group =
III.
Business
Type of Construction:
Fire Rating:
Roof =
Floor =
IV.
2.0 hr
2.0 hr
Live Loads:
Roof angle ()
0.00 / 12
0.0 deg
Roof
0 to 200 sf: 20 psf
200 to 600 sf: 24 - 0.02Area, but not less than 12 psf
over 600 sf: 12 psf
Floor
Stairs & Exitways
Balcony
Mechanical
Partitions
V.
Wind Loads :
50 psf
100 psf
100 psf
N/A
20 psf
ASCE 7 - 98
Importance Factor
Basic Wind speed
Directionality (Kd)
Mean Roof Ht (h)
Parapet ht above grd
Exposure Category
Enclosure Classif.
Internal pressure
Building length (L)
Least width
(B)
Kh case 1
Kh case 2
1.00
85 mph
0.85
255.0 ft
258.0 ft
B
Partially Enclosed
+/-0.55
130.0 ft
130.0 ft
1.291
1.291
Topographic Factor (Kzt)
Topography
Hill Height
(H)
Half Hill Length (Lh)
Actual H/Lh
=
Use H/Lh
=
Modified Lh
=
From top of crest: x=
Bldg up/down wind?
Flat
80.0 ft
100.0 ft
0.80
0.50
160.0 ft
50.0 ft
downwind
H/Lh= 0.50
K1 =
x/Lh = 0.31
K2 =
z/Lh = 1.59
K3 =
At Mean Roof Ht:
Kzt = (1+K1K2K3)^2 =
0.000
0.792
1.000
1.000
Company
JOB TITLE
Address
City, State
Phone
other
V.
Example 6 & 11 - 2000 IBC
JOB NO.
SHEET NO.
CALCULATED BY
DATE
CHECKED BY
DATE
Wind Loads - cont.:
Gust Effect Factor
h=
use this h :
B=
Calculated /z =
Use this /z :
Flexible structure if natural frequency < 1 Hz (T > 1 second).
However, rule of thumb is if h/B < 4 then rigid structure.
h/B = 1.96
Therefore, probably rigid structure
255.0 ft
255.0 ft
130.0 ft
153.0 ft
153.0 ft
G=
Rigid Structure
/ =
0.33
l=
320 ft
zmin =
30 ft
c=
0.30
gQ, gv =
3.4
Lz = 533.6 ft
Q=
0.81
Iz =
0.23
G=
0.83
0.88
Use flexible structure formula
Flexible or Dynamically Sensitive Structure
Natural Frequency (n1) =
0.5 Hz
Damping ratio () =
0.01
/b =
0.45
/ =
0.25
Vz =
82.3
N1 =
3.24
Rn =
0.067
=
Rh =
0.131
7.125
=
RB =
0.237
3.632
=
RL =
0.079
12.160
gR =
4.021
R =
0.342
G =
0.876
h = 255.0 ft
Enclosure Classification
Test for Enclosed Building: A building that does not qualify as open or partially enclosed.
Test for Open Building:
All walls are at least 80% open.
Ao 0.8Ag
Test for Partially Enclosed Building:
Input
Ao
0.0 sf
Ag
0.0 sf
Aoi
0.0 sf
Agi
0.0 sf
Ao 1.1Aoi
Ao > 4' / 0.01Ag
Aoi / Agi 0.20
Test
YES
NO
NO
Building is NOT Partially Enclosed.
Conditions to qualify as Partially Enclosed Building. Must satisfy all of the following:
Ao >= 1.1Aoi
Ao > smaller of 4' or 0.01 Ag
Aoi / Agi <= 0.20
Where:
Ao = the total area of openings in a wall that receives positive external pressure.
Ag = the gross area of that wall in which Ao is identified.
Aoi = the sum of the areas of openings in the building envelope (walls and roof) not including Ao.
Agi = the sum of the gross surface areas of the building envelope (walls and roof) not including Ag.
Reduction Factor for large volume partially enclosed buildings (Ri):
If the partially enclosed building contains a single room that is unpartitioned , the internal
pressure coefficient may be multiplied by the reduction factor Ri.
Total area of all wall & roof openings (Aog):
Unpartitioned internal volume (Vi) :
Ri =
0 sf
0 cf
1.00
Altitude adjustment to constant 0.00256 :
Altitude =
Constant =
0 feet
0.00256
Average Air Density =
0.0765 lbm/ft3
Company
JOB TITLE
Address
City, State
Phone
other
V.
JOB NO.
Surface Pressures (psf)
Surface
Windward Wall (WW)
Leeward Wall (LW)
Side Wall (SW)
Leeward Roof (LR)
Windward Roof: 0 to h/2*
> h/2*
DATE
CHECKED BY
DATE
GCpi =
G=
z for qi :
qi =
Wind Normal to Ridge (psf)
B/L = 1.00
h/L = 1.96
qhGCp
w/+qiGCpi w/-qhGCpi
Cp
0.80
14.2
see table below
-0.50
-8.9
-17.2
2.3
-0.70
-12.5
-20.7
-1.3
-1.04
-0.70
**
-18.5
-12.5
-26.8
-20.7
SHEET NO.
CALCULATED BY
Wind Loads - MWFRS all h (Enclosed/partially enclosed only)
Kh (case 2) =
1.29
h=
255.0 ft
Base pressure (qh) =
20.3 psf
ridge ht =
255.0 ft
Roof Angle =
0.0 deg
L=
130.0 ft
Roof tributary area - (h/2)*L: 16575 sf
B=
130.0 ft
(h/2)*B: 16575 sf
h=
Example 6 & 11 - 2000 IBC
-7.3
-1.3
Dist.*
+/-0.55
0.88
90.0 ft
15.1 psf for positive internal pressures
Wind Parallel to Ridge (psf)
L/B = 1.00
h/L = 1.96
qhGCp w/ +qiGCpi w/ -qhGCpi
Cp
0.80
-0.50
-0.70
0 to h/2*
> h/2*
14.2
-8.9
-12.5
see table below
-17.2
2.3
-20.7
-1.3
Included in windward roof
-1.04
-18.5
-26.8
-0.70
-12.5
-20.7
*Horizontal distance from windward edge
**Roof angle < 10 degrees. Therefore, leeward roof
is included in windward roof pressure zones.
Windward Wall Pressures at "z" (psf)
Combined WW + LW
Normal
Parallel
to Ridge
to Ridge
z
0 to 15'
17.5 ft
30.0 ft
42.5 ft
55.0 ft
67.5 ft
80.0 ft
92.5 ft
105.0 ft
117.5 ft
130.0 ft
142.5 ft
155.0 ft
167.5 ft
180.0 ft
192.5 ft
205.0 ft
217.5 ft
230.0 ft
242.5 ft
255.0 ft
258.0 ft
Kz
0.57
0.60
0.70
0.77
0.83
0.88
0.93
0.97
1.00
1.03
1.07
1.09
1.12
1.15
1.17
1.19
1.21
1.23
1.25
1.27
1.29
1.30
Kzt
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
Windward Wall
qzGCp
w/+qiGCpi w/-qhGCpi
6.3 psf
6.6
7.7
8.5
9.2
9.7
10.2
10.7
11.0
11.4
11.7
12.1
12.3
12.6
12.9
13.1
13.4
13.6
13.8
14.0
14.2
14.3
-2.0 psf
-1.7
-0.6
0.2
0.9
1.4
1.9
2.4
2.8
3.1
3.4
3.8
4.1
4.3
4.6
4.8
5.1
5.3
5.5
5.7
5.9
6.0
17.5 psf
17.8
18.9
19.7
20.3
20.9
21.4
21.8
22.2
22.6
22.9
23.2
23.5
23.8
24.0
24.3
24.5
24.8
25.0
25.2
25.4
25.4
NOTE:
See figure 6-9 of ASCE7 for the application of full and partial loading
of the above wind pressures. There are 4 different loading cases.
Parapet
z
258.0 ft
Kz
1.30
Windward parapet:
Leeward parapet:
Kzt
1.00
30.6 psf
-20.4 psf
qp (psf)
20.4
(GCpn = +1.5)
(GCpn = -1.0)
15.2 psf
15.5
16.6
17.4
18.1
18.6
19.1
19.5
19.9
20.3
20.6
20.9
21.2
21.5
21.8
22.0
22.3
22.5
22.7
22.9
23.1
23.2
15.2 psf
15.5
16.6
17.4
18.1
18.6
19.1
19.5
19.9
20.3
20.6
20.9
21.2
21.5
21.8
22.0
22.3
22.5
22.7
22.9
23.1
23.2
-7.3
-1.3
Company
JOB TITLE
Address
City, State
Phone
other
JOB NO.
V. Wind Loads - Components & Cladding : h > 60'
Kh (case 1) =
1.29
Base pressure (qh) =
20.3 psf
Roof Angle =
0.0 deg
h=
a=
GCpi =
qi =
Minimum parapet height at building perimeter =
Roof
Area
Zone 1
Zone 2
Zone 3
Example 6 & 11 - 2000 IBC
10 sf
-1.40
-2.30
-2.30
SHEET NO.
CALCULATED BY
DATE
CHECKED BY
DATE
255.0 ft
13.0 ft
NOTE: If tributary area is greater than
+/-0.55
700sf, MWFRS pressure may be used.
15.1 psf for positive internal pressures
3.0 ft
GCp
Surface Pressure (psf)
100 sf
500 sf
10 sf
100 sf
500 sf
-1.11
-0.90
-37 psf
-31 psf
-27 psf
-1.89
-1.60
-55 psf
-47 psf
-41 psf
-1.89
-1.60
-55 psf
-47 psf
-41 psf
Zone 3 = zone 2, since parapet >= 3ft.
User input
50 sf
250 sf
-33 psf
-28 psf
-49 psf
-43 psf
-49 psf
-43 psf
Walls
GCp
Surface Pressure at "h"
User input
Area
20 sf
100 sf
500 sf
20 sf
100 sf
500 sf
28 sf
55 sf
Negative Zone 4
-0.90
-0.80
-0.70
-26.6 psf
-24.5 psf
-22.5 psf
-26.2 psf
-25.3 psf
Negative Zone 5
-1.80
-1.40
-1.00
-44.8 psf
-36.7 psf
-28.6 psf
-43.2 psf
-39.7 psf
Positive Zone 4 & 5
0.90
0.75
0.60
18.3 psf
15.2 psf
12.2 psf
28.8 psf
27.5 psf
NOTE: Negative zones 4 & 5 pressures apply to all heights. Positive pressures vary with height, see below.
Wall surface pressure at "z"
z
Kz
Kzt
0 to 15'
0.70
1.00
17.5 ft
0.70
1.00
30.0 ft
0.70
1.00
42.5 ft
0.77
1.00
55.0 ft
0.83
1.00
67.5 ft
0.88
1.00
80.0 ft
0.93
1.00
92.5 ft
0.97
1.00
105.0 ft
1.00
1.00
117.5 ft
1.03
1.00
130.0 ft
1.07
1.00
142.5 ft
1.09
1.00
155.0 ft
1.12
1.00
167.5 ft
1.15
1.00
180.0 ft
1.17
1.00
192.5 ft
1.19
1.00
205.0 ft
1.21
1.00
217.5 ft
1.23
1.00
230.0 ft
1.25
1.00
242.5 ft
1.27
1.00
h= 255.0 ft
1.29
1.00
258.0 ft
1.30
1.00
Parapet
z
258.0 ft
qz (psf)
11.0
11.0
11.0
12.2
13.1
13.9
14.6
15.2
15.8
16.3
16.7
17.2
17.6
18.0
18.4
18.7
19.1
19.4
19.7
20.0
20.3
20.4
Kz
Kzt
qp
1.30
1.00
20.4 psf
CASE A = pressure towards building
CASE B = pressure away from building
Positive zone 4 & 5 (psf)
20 sf
100 sf
500 sf
21.1
19.4
17.8
21.1
19.4
17.8
21.1
19.4
17.8
22.1
20.3
18.5
23.0
21.0
19.0
23.7
21.6
19.5
24.3
22.1
19.9
24.8
22.6
20.3
25.3
23.0
20.6
25.8
23.4
20.9
26.2
23.7
21.2
26.6
24.1
21.5
27.0
24.4
21.7
27.4
24.7
22.0
27.7
24.9
22.2
28.0
25.2
22.4
28.3
25.5
22.6
28.6
25.7
22.8
28.9
25.9
23.0
29.2
26.2
23.2
29.4
26.4
23.3
29.5
26.4
23.4
Solid Parapet Pressure
CASE A : Interior zone:
Corner zone:
CASE B : Interior zone:
Corner zone:
10 sf
65.2 psf
65.2 psf
-36.7 psf
-55.0 psf
100 sf
53.7 psf
53.7 psf
-31.6 psf
-43.8 psf
500 sf
44.8 psf
44.8 psf
-26.5 psf
-32.6 psf
Company
JOB TITLE
Address
City, State
Phone
other
VI.
Seismic Loads:
Example 6 & 11 - 2000 IBC
JOB NO.
SHEET NO.
CALCULATED BY
DATE
CHECKED BY
DATE
IBC 2000
Seismic Use Group :
Importance Factor (I) :
Site Class :
Ss (0.2 sec) =
S1 (1.0 sec) =
I
1.00
D
150.00 %g
60.00 %g
Zip Code Search for Ss & S1:
[Link]
Fa =
1.000
Sms =
1.500
Sds =
1.000
Design Category =
Fv =
1.500
Sm1 =
0.900
Sd1 =
0.600
Design Category =
Seismic Design Category =
Number of Stories:
20
Structure Type: Not applicable
Plan Structural Irregularities: No plan Irregularity
Vertical Structural Irregularities: No vertical Irregularity
Flexible Diaphragms:
Building System:
Seismic resisting system:
System Building Height Limit:
Actual Building Height (hn) =
No
Dual Systems with special Moment Frames
Special reinforced concrete shear walls
Height not limited
255.0 ft
See Code section 1617.6.4 for exceptions and other system limitations
DESIGN COEFFICIENTS AND FACTORS
Response Modification Factor (R) =
8
System Over-Strength Factor () =
2.5
Deflection Amplification Factor (Cd) =
6.5
Sds =
1.000
Sd1 =
0.600
Code Reference Section for Detailing : 1910.2.4
Seismic Load Effect (E) = QE +/- 0.2SDS D
Special Seismic Load Effect (Em) = o QE +/- 0.2SDS D
= QE +/= 2.5 QE +/-
0.200D
0.200D
= redundancy coefficient
QE = horizontal seismic force
D = dead load
PERMITTED ANALYTICAL PROCEDURES
Index Force Analysis (Seismic Category A only)
Simplified Analysis
Method Not Permitted
Method Not Permitted
Equivalent Lateral-Force Analysis
Building period coef. (CT) =
Approx fundamental period (Ta) =
User calculated fundamental period (T) =
Seismic response coef. (Cs) =
need not exceed Cs =
but not less than Cs =
USE Cs =
Method Not Permitted
0.020
CThnx =
1.276 sec
2.94 sec
SdsI/R =
Sd1 I /RT =
0.044SdsI =
Model, Linear & Nonlinear Response Analysis
x= 0.75
0.125
0.049
0.044
0.049
Design Base Shear V = Method Not Permitted
- Permitted (see code for procedure)
ALLOWABLE STORY DRIFT
Structure Type:
Allowable story drift =
All other structures
0.020hsx
Cu = 1.20
Tmax = CuTa = 1.531
Use T = 1.531
where hsx is the story height below level x
Company
JOB TITLE
Address
City, State
Phone
other
VI.
Example 6 & 11 - 2000 IBC
JOB NO.
SHEET NO.
CALCULATED BY
DATE
CHECKED BY
DATE
Seismic Loads - cont. :
Seismic Design Category (SDC)= D
CONNECTIONS
Force to connect smaller portions of structure to remainder of structure
Fp = 0.133SDSwp =
or Fp = 0.5wp =
0.13 wp
0.05 wp
Use Fp =
0.13 wp
wp = weight of smaller portion
Beam, girder or truss connection for resisting horizontal force parallel to member
FP = no less than 0.05 times dead plus live load vertical reaction
Anchorage of Concrete or Masonry Walls to elements providing lateral support
Fp = 1.2IeSdsWw =
1.200 ww
or Fp = 0.1ww =
0.10 ww
Use Fp =
1.20 ww
but not less than
200.0 plf
= 400SdsIe
Connection force given is for flexible diaphragms (use architectural components for ridgid diaphrams)
MEMBER DESIGN
Bearing Walls and Shear Walls (out of plane force)
Fp = 0.40IeSDSww =
or Fp = 0.1ww =
0.400 ww
0.10 ww
Use Fp =
0.40 ww
Diaphragms
Fp = (Sum Fi / Sum Wi)Wpx + Vpx =
need not exceed 0.3 SdsIeWpx + Vpx =
but not less than 0.15 SdsIeWpx + Vpx =
(Sum Fi / Sum Wi)Wpx + Vpx
0.300 Wpx + Vpx
0.150 Wpx + Vpx
ARCHITECTURAL COMPONENTS SEISMIC COEFFICIENTS
Architectural Component : Cantilever Elements (Unbraced or Braced to Structural Frame Below Its Center of Mass)
Importance Factor (Ip) :
1.0
Component Amplification Factor (ap) =
Comp Response Modification Factor (Rp) =
Fp = 0.4apSdsIpWp(1+2z/h)/Rp =
not greater than Fp = 1.6SdsIpWp =
but not less than Fp = 0.3SdsIpWp =
2.5
2.5
h=
z=
0.557 Wp
1.600 Wp
0.300 Wp
255.0 feet
50.0 feet
use Fp =
MECH AND ELEC COMPONENTS SEISMIC COEFFICIENTS
z/h =
0.20
0.557 Wp
Seismic Design Category D & Ip=1.0, therefore
see 2000IBC Section 1621.1.1 for exceptions
Mech or Electrical Component : General Electrical - Distribution systems (bus ducts, conduit, cable tray)
Importance Factor (Ip) :
1.0
Component Amplification Factor (ap) =
Comp Response Modification Factor (Rp) =
Fp = 0.4apSdsIpWp(1+2z/h)/Rp =
not greater than Fp = 1.6SdsIpWp =
but not less than Fp = 0.3SdsIpWp =
1
3.5
0.159 Wp
1.600 Wp
0.300 Wp
h=
z=
255.0 feet
50.0 feet
use Fp =
z/h =
0.300 Wp
0.20
Company
JOB TITLE
Address
City, State
Phone
other
Example 6 & 11 - 2000 IBC
JOB NO.
SHEET NO.
CALCULATED BY
DATE
CHECKED BY
DATE
[Link]
CODE SUMMARY
Code:
International Building Code 2000
Live Loads:
Roof
Floor
Stairs & Exitways
Balcony
Mechanical
Partitions
0 to 200 sf: 20 psf
200 to 600 sf: 24 - 0.02Area, but not less than 12 psf
over 600 sf: 12 psf
50 psf
100 psf
100 psf
N/A
20 psf
Dead Loads:
Floor
Roof
72.4 psf
77.8 psf
Roof Snow Loads:
Design Roof Snow load
Flat Roof Snow Load
Snow Exposure Factor
Importance Factor
Thermal Factor
Ground Snow Load
Rain on Snow Surcharge
Sloped-roof Factor
=
=
=
=
=
=
=
Cs =
Pf
Ce
I
Ct
Pg
8.5 psf
5.0 psf
1.00
1.00
1.00
5.0 psf
3.5 psf
1.00
Wind Design Data:
Basic Wind speed
Mean Roof Ht (h)
Building Category
Importance Factor
Exposure Category
Enclosure Classif.
Internal pressure Coef.
Directionality (Kd)
85 mph
255.0 ft
II
1.00
B
Partially Enclosed
+/-0.55
0.85
Earthquake Design Data:
Seismic Use Group :
Importance Factor
Mapped spectral response
accelerations
Site Class
Spectral Response Coef.
Seismic Design Category
Basic Structural System
Seismic Resisting System
Design Base Shear
Seismic Response Coef.
Response Modification Factor
Analysis Procedure
=
I
I =
1.00
Ss =
150.00 %g
S1 =
60.00 %g
=
D
Sds =
1.000
Sd1 =
0.600
=
D
= Dual Systems with special Moment Frames
= Special reinforced concrete shear walls
V =
0.049W
Cs =
0.049
R =
8
= Equivalent Lateral-Force Analysis
CODE SUMMARY- continued
Component and cladding wind pressures
Select method :
C&C>60 feet
Roof
Area
Negative Zone 1
Negative Zone 2
Negative Zone 3
Wall
Area
Negative Zone 4
Negative Zone 5
Positive Zone 4 & 5
0 to 15'
18 ft
30 ft
43 ft
55 ft
68 ft
80 ft
93 ft
105 ft
118 ft
130 ft
143 ft
155 ft
168 ft
180 ft
193 ft
205 ft
218 ft
230 ft
243 ft
255 ft
258 ft
Surface Pressure (psf)
10 sf
50 sf
100 sf
-36.7
-30.7
-26.6
-55.0
-46.6
-40.8
-55.0
-46.6
-40.8
Surface Pressure (psf)
20 sf
50 sf
100 sf
-26.6
-24.5
-22.5
-44.8
-36.7
-28.6
21.1
21.1
21.1
22.1
23.0
23.7
24.3
24.8
25.3
25.8
26.2
26.6
27.0
27.4
27.7
28.0
28.3
28.6
28.9
29.2
29.4
29.5
19.4
19.4
19.4
20.3
21.0
21.6
22.1
22.6
23.0
23.4
23.7
24.1
24.4
24.7
24.9
25.2
25.5
25.7
25.9
26.2
26.4
26.4
17.8
17.8
17.8
18.5
19.0
19.5
19.9
20.3
20.6
20.9
21.2
21.5
21.7
22.0
22.2
22.4
22.6
22.8
23.0
23.2
23.3
23.4