Wind Analysis
Wind Analysis
Buildings
Study Project Report
By
BITS Pilani
May 2016
1
Contents
ACKNOWLEDGEMENT ................................................................................................................................................. 3
INTRODUCTION .......................................................................................................................................................... 4
INDIAN STANDARD CODE -IS 875: PART3 ................................................................................................................... 9
Basic Wind Speed: ............................................................................................................................................. 10
Design Wind Speed: .......................................................................................................................................... 10
Probability factor (risk coefficient) (k1) ....................................................................................................... 11
Terrain, Height and Structure Size factor (K2) ............................................................................................. 11
Topography factor (K3) ................................................................................................................................ 12
Importance Factor for Cyclonic Region (k4) ................................................................................................. 13
Wind Pressure ................................................................................................................................................... 13
Design Wind Pressure ....................................................................................................................................... 14
Wind Forces on individual members ................................................................................................................ 14
Wind Forces on structure.................................................................................................................................. 15
Dynamic Effects................................................................................................................................................. 15
Gust Factor ........................................................................................................................................................ 17
Cross wind Response ........................................................................................................................................ 19
Difference between IS 875:1987 and 2009 (draft) .............................................................................................. 20
ASCE-7: Minimum Design Loads for Buildings and Other Structures (American code) (2002) ......................... 21
Some Basic Concepts ........................................................................................................................................ 21
1. Basic Wind Speed (V) ........................................................................................................................... 21
2. Exposure Category................................................................................................................................ 22
3. Topographic Factor (KZI) ....................................................................................................................... 23
4. Gust Factor (G or Gf) ............................................................................................................................. 24
Method 1 - Simplified Procedure ...................................................................................................................... 25
Method 2 - Analytical Procedure ...................................................................................................................... 27
Method 3 - Wind Tunnel Procedure ................................................................................................................. 28
Example: ............................................................................................................................................................ 29
1. Structural Data ..................................................................................................................................... 30
2. Properties ............................................................................................................................................. 31
3. Load Combination factors .................................................................................................................... 32
4. Auto Load Calculations Using ETABS 2015 .......................................................................................... 32
5. Analysis ................................................................................................................................................. 41
6. Displacements due to Wind Loads....................................................................................................... 43
Summary ........................................................................................................................................................... 45
Conclusion ......................................................................................................................................................... 47
References ........................................................................................................................................................ 48
2
ACKNOWLEDGEMENT
3
INTRODUCTION
This Study Project covers some essential study regarding wind loads and related
different codal provisions related to wind and load considered in designing of buildings due to
wind. Study of Indian Standard code (IS [Link]- Part 3) as well as (IS 875:2009 part 3-draft)
is explained in this report. American Code for wind loads (ASCE-7:2002 version) and its
comparison with Indian codes is also included in this report.
Some properties and facts related to tall buildings, wind and variation of wind with
respect to its height are introduced below which will give necessity of wind loads on tall
buildings.
TALL BUILDINGS
There is no absolute definition of what constitutes a tall building according to
Council of Tall Buildings and Urban Habitat (CTBUH).Height is relative concept, i.e. a building
which should be considered as tall building in country like India may not considered as tall in
case of tall buildings countries like US(Chicago). Measurement of height of Tall Building can
be considered by three methods according to CTBUH. :-
4
2. Height to Tip
Height is measured from the level of the lowest, significant, open-
air, pedestrian entrance to the highest point of the building, irrespective of material
or function of the highest element (i.e., including antennae, flagpoles, signage, and
other functional technical equipment).
Note: - A building having height more than 15 m is considered as tall building according to
National Building Code 2005 of India is Called Tall building. (High Rise Building).
Building having height more than 18 m (60ft.) is considered as tall building according to
American code ASCE-7: 2002 version. Building having mean roof height more than least
horizontal dimension is also considered as tall building according to this American code.
5
WIND
Wind is air in motion relative to the surface of the earth. Primary
reasons of wind is rotation of earth as well as due to difference in terrestrial radiation.
Over 50 years study of wind and its speed is carried out in different places to find mean
wind speed in different places so that it can be used in further calculations of wind loads
which is listed in IS 875:Part3 -1997 as well as in 2009 draft version. This study is carried
out using anemometers or anemographs which are installed in different meteorological
stations at height of 10 m- 30 m. According to this study India is divided into six different
categories depending upon basic wind speeds in each zone. Average basic speeds as per
IS875 is given in table 1.
Some parts of Jammu and Kashmir as well as Mizoram and Tripura. 55 m/s
Whole eastern Coastal area, Costal part in Gujarat as well as Assam. 50 m/s
Some part of Tamil Nadu and almost Half North India which includes part of Gujarat ,whole 47 m/s
Rajasthan ,Punjab ,part of Madhya Pradesh, Utter Pradesh ,Bihar ,Part of Jharkhand, West
Bengal and Sikkim.
Western coastal area in Maharashtra as well as some inside land near eastern costal area which 44 m/s
is part of Andhra Pradesh ,Maharashtra and Orissa and some eastern part of India , that is ,
Nagaland , Manipur and Mizoram.
Most of the Middle and South India. 39 m/s
Some part of Karnataka, Kerala, Andhra-Pradesh, Telangana and Tamil Nadu which is mostly 33 m/s
land between eastern and western costal area.
Table1-According to IS875:1997 - Part3
6
WIND AND ITS VARIATION WITH HEIGHT
Wind speeds are generally very low near earth surface due to earth friction.
It increases with height from zero to some value and then it remains almost constant. At
some height wind can be considered as free from
earths atmosphere which leads to almost constant
velocity after certain height. This height is known as
Fetch Height or Gradient Height.
7
As per CTBUH, Tall buildings ae also classifies as supertall and mega tall
buildings. Supertall building is a building having height over 300 m (984 feet) while Mega
building is one which has height over 600 m (1968 feet).There were total 91 supertall
buildings and 2 Mega buildings in world till June [Link] mostly high populated cities
are coming up with many tall structures. For seismic loads, earthquake loads are usually
known to people but wind loads also plays important role near coastal areas as discussed
above. There are many areas damaged due to cyclones. Wind speed increases with
height from ground surface and hence its impact which eventually leads to Wind as
major factor in consideration for case of tall buildings. Increasing number of tall
structures and unawareness of people regarding wind loads makes this study very
important.
This report will describe about IS 875:1987 Part 3 which is mainly code used
for designing wind loads in India. Calculation of design wind speeds, design wind
pressure followed by design wind pressure , some Oscillation related phenomenon like
Galloping , flutter ,Ovaling ,Vortex Shedding , etc. according to IS 875:1987 part 3 as
well as few changes made in IS 875:2009 Part-3 (draft form) which includes
Interference effect, Dynamic Response Factor ,Cross wind response ,etc.
This report will also describe about American code for Wind Loads, ASCE-
7:2002 version, Wind loading part. Three different methods, i.e. Simplified Procedure,
Analysis Procedure and Wind Tunnel Testing will be described in the report along with
its limitations.
8
INDIAN STANDARD CODE -IS 875: PART3
IS 875 was first published in 1957 for the guidance of civil engineers,
designers and architects associated with the planning and design of buildings which was
included the provisions for the basic design loads (dead loads, live loads, wind loads and seismic
loads) to be assumed in the design of the buildings. In its first revision in 1964, the wind pressure
provisions were modified on the basis of studies of wind phenomenon and its effect on
structures, undertaken by the special committee in consultation with the Indian Meteorological
Department. Similarly in 1987 code many changes carried out which leads to better design of
building for wind loads and continuous studied related wind made another version of this code
in 2009 which is still in its draft form.
BSCP 3:1973 Code of basic data for design of buildings: Chapter 5 Loading: Part 2: Wind
loads
NZS 4203-1976 Code of Practice for general structural design loading for buildings
ANSI A58.1-1972 American Standard Building code requirements for minimum design
loads in buildings and other structures
Wind resistant design regulations, a world list. Association for Science Documents
Information, Tokyo.
9
Basic Wind Speed:
India is divided in 6 zones according to Basic wind velocity which is
applicable for height about 10 m from mean ground level which is explained in
introduction of wind.
In Appendix A, IS 875: Part3 -1987 (as well as 2009), Basic wind speed
(Vb) for some important cities is listed by studying wind speeds over 50 years.
Where
10
Probability factor (risk coefficient) (k1)
1
XN,PN AB[ln{ ln(1PN)}]
N
K1=X50,063= A+4B
Where,
a. Types of Terrain:
Classified in Four different terrains as follows:-
a) CATEGORY 1:- Exposed Open terrain with few or no obstructions.
b) CATEGORY 2:- Open terrain with well scattered obstructions.
c) CATEGORY 3:- Terrain with numerous closely spaced obstructions.
d)CATEGORY 4:- Terrain with numerous large high closely spaced
obstructions
11
b. Classes of Buildings:
Buildings can be classified in three different classes depending upon size
factor:-
a) Class A:-Structure and/or its component having its maximum dimension
less than 20 m.
b) Class B: - Structure and/or its component having its maximum dimension
between 20 m and 50 m.
c) Class C: - Structure and/or its component having its maximum dimension
greater than 50 m
The velocity profile for a given terrain category does not develop to
full height immediately with the commencement of that terrain category but
develop gradually to height ( h, ) which increases with the fetch or upwind distance
(x). The relation between the developed height (h,) and the fetch (x) for wind-flow
over each of the four terrain categories is given in IS 875. For structures of heights
greater than the developed height (h,) the velocity profile may be determined in
accordance with the less or least rough terrain, or another procedure is given in
Appendix B of IS 875:1987-part3
This is factor for taking local topographic feature like cliffs, hills
valleys, etc. into consideration while calculating design wind speed. This factor is
effective when upwind slop () is greater than 3o. Value of K3 is i) 1 when < 3o ii)
1.36 when > 17o. And for 3 o < < 17 o It can be given by:-
K3 =1 + Cs
12
Importance Factor for Cyclonic Region (k4)
Wind Pressure
13
Design Wind Pressure
Design Wind pressure according to IS875:1987 part3 is same as
wind pressure explained above. In IS 875:2009 part3 few new factors like wind
directionality factor, area averaging factor, Combination factor are introduced to make
design economical, hence design pressure is different than wind pressure which is given
by following formula:-
Pd =[Link] .Pz
Where
Pd = design wind pressure in N/m2 at height z.
Pz = wind pressure in N/m2 at height z.
Kd = wind directionality factor.
Ka = area averaging factor.
Kc = Combination factor.
F = (Cpe Cpi) A pd
Where
Pd = design wind pressure in N/m2 at height z.
Cpe = external pressure coefficient.
Cpi = internal pressure coefficient.
A = Surface area of structural element
Internal and external pressure coefficients for different units having different
shapes, structures and slopes are described in IS 875 with figures.
14
Wind Forces on structure
The value of force coefficients apply to a building or
structure as a whole, and when multiplied by the effective frontal area A, of the
building or structure and by design wind pressure, pd gives the total wind load
on that particular building or structure.
F = (Cf) A pd
Where
Pd = design wind pressure in N/m2 at height z.
Cf = force coefficient of building.
A = Surface area of structural element.
Force Coefficient:
Dynamic Effects
For tall, long span and slender structures, wind Fluctuations
causes fluctuating forces on structure which induces large dynamic motions
including oscillations. Wind loads can induce both along wind Oscillations as well
As crosswind Oscillations (vortex shedding). Along wind Oscillations are
calculated more readily. Estimation of Vortex shedding has been introduced in IS
875: 1987 but is still not developed enough.
Flexible slender structures and structural elements have to
investigate for oscillating effects cause due to wind loadings. Criteria for
examining structure or building need not necessary if buildings and closed
structures having ratio of height to minimum lateral dimension, more than 5
OR natural frequency of buildings and closed structures in first mode is less
than 1Hz.
15
i) Fundamental time period (T):
T=0.1n
SVd
= b
S=Strouhal number.
Vd=Design Wind velocity.
b=breadth of structure or
structural member in
horizontal plane normal to
wind direction.
Circular sections
S=0.2 for Vz 7
S=0.25 for Vz > 7
Rectangular Structures
S=0.15
Gust Factor
IS 875:1987 allows Gust method for calculation of wind loads some cases .This
method needs Hourly mean wind speed which is equal to basic wind speed. Wind load
can be calculated from Gust factor method by using following formula:-
= ()
Fz = along wind load on the structure at any height z corresponding to strip area Ae
17
G=Gust factor =
G=1+gtr(1 + )2 +
Where
gf = peak factor defined as the ratio of the expected peak value to the
root mean value of a fluctuating load
=
4
18
Cross wind Response
This factor is defined in IS 875: 2009 draft version .The equivalent
crosswind static force per unit height (We) as a function of z in Newton per
meter height, shall be as follows:
We (z) = 0.6 [Vh] 2 d Cdyn
Where,
d = Lateral dimension of the structure parallel to the wind stream, and
b
Cdyn = 1.5gR 1+ ()k ( )
Where,
Km = mode shape correction factor = 0.76 + 0.24 k
Where
k = mode shape power exponent for the fundamental mode of
vibration
= 1.5 for a uniform cantilever
= 0.5 for a slender framed structure (moment resistant)
= 1.0 for building with central core and moment resisting faade
= 2.3 for a tower decreasing in stiffness with height, or with a large
mass at top
Cfs = crosswind force spectrum coefficient generalized for a linear
mode shape.
GR = peak factor for resonant response (1 hour period) given by
GR = [2 log (3600f0)] ()
= ratio of structural damping to critical damping of Structure
Ih = turbulence intensity, obtained by setting z equal to h
gv = peak factor for the upwind velocity fluctuations, which shall be
taken as 3.5
19
Difference between IS 875:1987 and 2009
(draft)
For calculation of wind speed K4 factor for cyclone is introduced in 2009 version.
Design Wind Pressure is same as wind pressure in case of 1987 code but for 2009 version
three new factors are introduced. Design pressure can be obtained by multiplying this
factors by wind pressure. This three factors are
a)Kc=combination factor
Interference effect is introduced in 2009 code while it was not in 1987. When wind comes
from striking some buildings and original wing may have some phase difference which will
leads to interference effect.
Dynamic Response Factor will tell you wind pressure at certain height of building. In the
1987 version, the dynamic response factor, Cdyn, was applied to the wind loading due to
hourly mean wind speed, as opposed to the 3second gust speed used in the 2009 version.
20
ASCE-7: Minimum Design Loads for Buildings
and Other Structures (American code) (2002)
This Code is published by American Society for Civil Engineers. As per name
of code this is made for design of all kinds of loads like dead, live, soil, flood, wind, snow,
rain, ice and earthquake loads. In this report mainly we will focus on wind load designing.
The design wind loads for buildings and other structures, including the main
wind force-resisting system and component and cladding elements thereof, shall be
determined using one of the following procedures: 1) Method 1 - Simplified Procedure
2) Method 2 Analytical Procedure
3) Method 3 Wind Tunnel Procedure
21
Atlantic coasts, the Caribbean or Hawaii). The resulting design speed by this
methods shall not be less than resulting 500 year return period wind speed divided
by 1.5 .
2. Exposure Category
The characteristics of ground roughness and surface irregularities are the
important factors to be considered while designing wind loads. This factors are
included in exposure category which will also take ground variation due to natural
topography and vegetation.
Surface Roughness Category: There are three major categories of surface
roughness as follows
Surface Roughness B: Urban and suburban area, wooded areas or other
terrain with numerous closely spaced obstructions having size of single family
dwelling or larger.
Surface Roughness C: Open terrain with scattered obstructions having
heights generally less than 30ft. (9.1 m). This category also includes flat open
country, grasslands, and all water surfaces in hurricane-prone regions.
Surface Roughness D: Flat, unobstructed and water surfaces outside
hurricane-prone regions. This category also includes smooth mud flats, salt flats,
and unbroken ice.
Transition Zone: For a site located in between any two or more exposure
categories, the category resulting largest wind force should be considered.
Intermediate exposure is permitted in case of rational analysis.
2. The hill, ridge, or escarpment protrudes above the height of upwind terrain
features within a 2-mile (3.22-km) radius in any quadrant by a factor of two or
more.
3. The structure is located in the upper half of a hill or ridge or near the crest of an
escarpment.
4. H/LH 0.2.
5. H is greater than or equal to 15 ft. (4.5 m) for Exposures C and D and 60 ft. (18
m) for Exposure B.
Topographic Factor. The wind speed-up effect shall be included in the calculation
of design wind loads by using the factor Kzt which can be calculated as follows:
Kzt= (1+K1K2K3)2
23
4. Gust Factor (G or Gf)
In this code Gust Factors are given for rigid structures as wells as for
flexible structures as given below:-
lz = c(33/z)1/6
Where,
24
Method 1 - Simplified Procedure
To design any building or structure by this method, it should satisfy few
conditions mentioned as follows:-
25
Design Procedure:-
1. Determine Basic Wind Speed, Importance factor I, exposure category, and
exposure adjustment coefficient from code.
2. Main Wind Force-Resisting System:-Simplified design wind pressure (ps) can be
given by following formula:
ps = Ips30
Where,
= adjustment factor for building height and Exposure
I = importance factor
pS30 = simplified design wind pressure for exposure B, at h = 30
ft, and for I = 1.0.
Note:-ps should not be less than 10lb/ft2 (0.48 kN/m2). This force is applied on
horizontal and vertical projections of building surfaces.
3. Component and Cladding:-Net design wind pressure (pnet) can be given by
following formula:
Pnet = Ipnet30
Where,
= adjustment factor for building height and Exposure
I = importance factor
pnet30 = simplified design wind pressure for exposure B, at h =
30 ft, and for I = 1.0.
Note:-Positive pnet should not be greater than 10lb/ft2 (0.48 kN/m2) and negative
pnet should not be less than -10lb/ft2 (-0.48 kN/m2). This force is applied normal
to each building surfaces.
26
Method 2 - Analytical Procedure
To design any building or structure by this method, it should satisfy few
conditions mentioned as follows:-
27
Method 3 - Wind Tunnel Procedure
Wind Tunnel Testing is used to determine
wind loads on any buildings and structures. This method is
useful in prediction of wind loads and responses of structures,
structural components, and cladding to verify the wind
conditions and hence to design any building or structure.
Problem with this method is its cost, i.e. it is very expensive.
28
Example:
Reinforced Concrete (RCC) frame with flat roof is designed using ETABS 2015
software having following dimensions:-
Component Length (in m.) Width (in mm.) Depth (in mm.)
3D View
Note: - No additional Dead loads and Live Loads are considered as their value is 0 kN/m2.
29
1. Structural Data
Data related to structure is provided in Table given below:-
a. Story Data:
b. Mass:
30
Table: Centre of Mass Calculations
UX UY UZ
Story
kg kg kg
Story10 273531.07 273531.07 0
Story9 294293.59 294293.59 0
Story8 294293.59 294293.59 0
Story7 294293.59 294293.59 0
Story6 294293.59 294293.59 0
Story5 294293.59 294293.59 0
Story4 294293.59 294293.59 0
Story3 294293.59 294293.59 0
Story2 294293.59 294293.59 0
Story1 297259.66 297259.66 0
Base 23728.6 23728.6 0
2. Properties
a. Materials:
b. Frame Sections:
c. Shell Sections:
d. Reinforcement Sizes:
31
3. Load Combination factors
Load combination factors used while analysing are listed below. This factors are taken
for DL+LL+WL combination from IS 456 for Indian case and from ASCE-07:2002 for
American case.
Table: Load Combination Factors from IS456
Name Load Case/Combo Scale Factor Type Auto
DD+LL+WL (Indian) Dead 1.2 Linear Add No
DD+LL+WL (Indian) Live 1.2 No
DD+LL+WL (Indian) Wind Indian 1.2 No
Assuming frame is located near Orissa, where basic wind speed Vb is 50 ms-1 as per
given in IS875:1987. Other assumed parameters are as follows:-
Risk Coefficient, k1 1
Topography Factor, k3 1
32
Case-1
Case-2
33
b. ASCE 7-02 Auto Wind Load Calculations:
Assuming frame is located is in America having same Basic Wind Speed as in Orissa i.e.,
Vb is 50 ms-1 (111.85mph). Other assumed parameters are as follows:-
34
Case-1
35
Case-1
36
Case-2
37
Case-2
38
Case-3
39
Case-4
40
5. Analysis
a. Base Reaction Calculations:
Load Case/Combo FX(kN) FY(kN) FZ(kN) MX(kN-m) MY(kN-m) MZ(kN-m) X(m) Y(m) Z(m)
Dead 0 0 28918.5181 176287.2864 -352575 0 0 0 0
DD+LL+WL (Indian) Max 0 0 34702.2217 245505.1329 -423089 5837.2475 0 0 0
DD+LL+WL (Indian) Min -957.5537 -1892.1115 34702.2217 211544.7437 -440276 -23068.6228 0 0 0
DD+LL+WL (American) Max 0 962.9247 34702.2217 239404.7455 -423089 14710.6433 0 0 0
DD+LL+WL (American) Min -649.7518 -1547.1356 34702.2217 194045.4059 -434897 -18862.6773 0 0 0
b. Story Forces:
i. Shear Diagrams
Shear Forces increases from top to bottom for [Link] table shows shear
forces for different cases which are calculated for story 1 :-
41
ii. Moment Diagrams
Moments increases from top to bottom for [Link] table shows Moments for different
cases which are calculated for story 1 :-
42
6. Displacements due to Wind Loads
Deformation Diagrams
Maximum joint displacements for different cases are shown in following table :-
Story UZmax(mm
Load Case/Combo UXmax(mm) UYmax(mm) RXmax(rad) RYmax(rad) RZmax(rad)
no. )
Dead 10 -2.23E-08 -2.59E-08 -5.43E+00 3.08E-04 2.92E-04 0
DD+LL+WL (Indian) Max 10 1.68E+01 3.79E+01 -6.52E+00 3.70E-04 -2.91E-04 0
DD+LL+WL (Indian) Min 10 -2.77E-08 -3.21E-08 -6.52E+00 -4.87E-03 3.51E-04 0
DD+LL+WL (American) Max 10 3.51E-04 3.32E+01 -6.52E+00 2.90E-03 1.69E-03 8.03E-04
DD+LL+WL (American) Min 10 -5.02E+00 -2.24E+01 -6.52E+00 -4.30E-03 -6.91E-04 -8.03E-04
15
10
0
211
253
295
337
1
15
29
43
57
71
85
99
113
127
141
155
169
183
197
225
239
267
281
309
323
351
-5
Joint numbers (from story10 to story1)
43
Displacement of joints in Y Direction
40
211
253
295
337
1
15
29
43
57
71
85
99
113
127
141
155
169
183
197
225
239
267
281
309
323
351
-5
Joint numbers (from story10 to story1)
1
15
29
43
57
71
85
99
113
127
141
155
169
183
197
211
225
239
253
267
281
295
309
323
337
351
-1
-2
-3
-4
-5
-6
-7
Joint numbers (from story10 to story1)
As Shown in above Graphs, Displacement in all direction is maximum for Indian DD+LL+WL
combination, while it is least is case of X & Y direction for dead loads. For American DD+LL+WL
combination, Displacement is least in Z direction as compared to other cases.
In all three cases, Maximum displacement is found to be for top story, i.e. for story 10. It
decreases with height.
44
Summary
Wind Load increases with increase in height and its direction is horizontal hence it is
important to analyse Tall buildings for wind loads.
IS 875:1987 Part 3 is Indian Standard Code for design of wind loads. IS 875:2009 part 3 is
in draft version, having few changes in it as compared to IS875:1987 part3.
ASCE -07 Chapter 6 is meant for design of wind loads. 2002 version of this code is used
in this report while 2005, 2010 versions of this codes are also available.
For IS 875:1987 and 2009 (part 3) versions, some major points for designing wind loads
are as follows:-
o Determining basic wind speed and hence design wind speed depending upon
height of building, terrain, topography, etc. (in case of 2009, cyclone zone also
considered).
o Determining Wind pressure and Design wind pressure for calculated design
velocity.
o Determining force coefficients and hence wind forces on buildings as well as for
individual members.
o This code is yet to be developed for considering Dynamic effects except vortex
shedding.
For ASCE-07:2002 version, some major points for designing loads are as follows:-
There are three different methods for this code
o Simplified method:-This is similar to IS 875 method. It needs to determine Basic
Wind Speed, Importance factor I, exposure category, and exposure adjustment
coefficient for calculation of wind loads. This is applicable for limited cases of
buildings and structures.
o Analytical method: - in this method some more factors as compared to simplified
method are taken into account. This can be applicable for most of the buildings
and structure.
o Wind Tunnel method: - This is method in which, actual model of building or
structure for which wind loading is to be designed. Wind conditions are applied
considering scale factors and making same environment as that of actual
building. Response of building and its components are observed and building or
structure is designed.
45
Some Observations from case studied for same conditions using IS875:1987 and ASCE-
7:02
o Wind Load for structure is calculated for 2 time taking only 1 case using IS 875:
part3 while it is calculated for 12 times considering 4 different cases in case of
ASCE-07:2002.
o Base reactions as well as Shear forces in Y directions are zero as per IS 875 but it
have positive value in case of ASCE-07.
o Moments for both codes are almost equal.
o Joint displacements are more in case of IS codes that displacements calculated
as per ASCE: 07.
46
Conclusion
ASCE:07 allows to use basic wind data by studying and analysing wind data which means more
accurate local conditions can be considered and hence structure may be more economical as
well as more strong. Local weather data study and its analysis should be allowed in Indian
Codes too.
Gust Factor method in IS 875 which is somewhat similar to analysis method in ASCE-07:2002 is
yet to be developed fully as compared to ASCE code.
Wind Tunnel procedure allowed in case or American code. Indian codes should also contain
wind tunnel procedure in case of designing tall buildings mostly in metro cities where tall
building can be designed considering all factors which will reduce risk for buildings.
ASCE-07 consider 4 cases while IS875 consider only two cases to determine design wind
pressure. Indian code should improve for determining wind load taking more cases, as more
cases mean more precision and hence less risk.
American code is more effective for designing for wind loads as it gives less deformation as
compared to Indian code. Less deformation means less chance for failure.
47
References
1. Council of Tall Building and Habitat (CTBUH) website.
2. Indian Standard Code:-Code of practice for design loads (other
than earthquake) for buildings and structures- IS875:1987 Part
3
3. Indian Standard Code Draft version- IS 875:2009 Part 3 draft
version with commentary.
4. American Code: Minimum Design Loads For Buildings and other
structures. (ASCE-7:2002 version)
5. [Link]
48