Saudi Aramco Jubail refinery
4100025840
Saudi Aramco Jubail refinery
4100025840
Saudi Aramco Jubail refinery
4100025840
Saudi Aramco Jubail refinery
4100025840
FUGITIVE EMISSION TEST
Report No: 068
FUGITIVE EMISSION TEST REPORT ACC TO SPEC
77/312 Insp Date: 29.06.2024
Name of the Client SVR GLOBAL MATERIAL WCB
SOLUTIONS INDIA
Job Description VALVE CLASS 150
PROJECT SHELL EFA/STOCK TYPE CHECK
Tracer Gas Helium Gas TESTED QTY 1
Helium Gas Purity 99.999% SIZE 4’’
Holding time 15 mins
Acceptance criteria 1.00*10-4 Acceptance criteria & Test As per Customer
Pressure Reference
INSTRUMENT DESCRIPTION:
Instrument Details Helium Leak Detector Standard Leak Make Pfeiffer Vacuum
Make PFEIFFER VACUUM PartNo FV4810
Model/[Link] ASM 310/HLD1701386 [Link] FC19000937
Measuring Range 5.0X10-11mbar.l/s Caldate/Duedate 03.01.2024/02.01.2025
Machine Sensitivity 1.0X10-11mbar.l/s Standard Leak Rate 2.2X10-8mbar.l/s
Caldate/Duedate 03.01.2024/02.01.2025 Measured Leak Rate 2.1X10-8mbar.l/s
Testing Details:
Valve [Link] Test Atmosphere Body bonnet leakage(mb.l/s) Packing leakage (mb.l/s)
Pressure leak
23G126206 20bar 2.8X10-6 4.9X10-6 -
RefStdSpec: MESC SPEC 77/312
TEST RESULT :The above mentioned valves has been Helium leak tested and observed leak rates are found to be
within the acceptable limit.
PERFORMEDBY: DEVANAND .P
ASNT LEVEL-II(LT) CLIENT/INSPECTED BY:
ShopA4,PlotNo-52,GroundFloor,NolamburPhase-II,3rdMainRoad [Link].:+919944412370
REPORT NO:APT/RT/23/24
SWING CHECK VALVE ,DN20,CL150, WCB,
FLANGED
REPORT NO:APT/RT/16/24
GATE VALVE ,DN100,CL300, WCB,
FLANGED