Manual TA4

The document is an operating manual for the TA4/2 analog transmitter, detailing its connections, specifications, calibration procedures, and installation guidelines. It emphasizes compliance with electromagnetic compatibility standards and provides information on load cell connections, output types, and adjustments for zero and full scale. Additionally, it includes maintenance instructions and disposal recommendations for the device.

Uploaded by

estebanlerez
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
96 views1 page

Manual TA4

The document is an operating manual for the TA4/2 analog transmitter, detailing its connections, specifications, calibration procedures, and installation guidelines. It emphasizes compliance with electromagnetic compatibility standards and provides information on load cell connections, output types, and adjustments for zero and full scale. Additionally, it includes maintenance instructions and disposal recommendations for the device.

Uploaded by

estebanlerez
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

CONNECTIONS

ANALOG TRANSMITTER
OPERATING MANUAL
MO.TA4.516.R4
SUGGESTION
For the full correspondence to the electromagnetic
compatibility, turn the screen inside each fairlead in order to
Load cells GB have it in contact with the case connected to the line Earth.

2 mV/V Analog TERMINALS


Output 1-2 = SIGNAL+ (S+) 10 = OUTPUT Volt
3-4 = SIGNAL- (S-) 11 = External ZERO potentiometer
5-6-7 = EXCITATION- (0V) 12 = OUTPUT mA
8-9 = EXCITATION + (+V) 13 = -POWER SUPPLY (0Vdc)
14 = +POWER SUPPLY (24 Vdc)
Vetek AB Box 79, Industriv. 3 760 40 Väddö Tel 0176 208 920,
EN ISO 9001 (2000)
Fax 0176 208929 e-mail: [email protected] www.vetek.net IQ-1100-01

DECLARATION OF CONFORMITY CONNECTIONS: Feeding, Load cells, Analog output and Zero potentiometer
According to the ISO/IEC guide and EN 45014

Manufacturer: AEP transducers s.r.l.


Address: Via Bottego 33/A 41010 Cognento MODENA Italia
DECLARES THAT THE FOLLOWING PRODUCT: 10KΩ
Device model: TA4/2
Device type: ANALOG TRANSMITTER WARNING
Year of manufacturring: 2004 connect a F type
Options: this declaration covers all the options specified in the sales cataloque. fuse by 500mA
CONFORMS TO THE FOLLOWING NORMS: EN 61010-1 EN 61326-1 EN61326/A1 250V on the
The product has been tasted in the typical installation configuration, as described in the feeding.
instruction manual.
TA4D/2 model: the immunity to the electromagnetic fields is 3V/m.
Above described product meets the requirements of mentioned Norms, basing on both
test esult and considerations listed in the technical file.
I declare that above defined product meets the requirements of the:
89/336/CEE - 92/31/CEE - 93/68/CEE - 73/23/CEE.
41010 Cognento MODENA 07/07/2004
Lioi Giovanni
Technical Manager

INTRODUCTION SETTINGS
TA4/2 transmitters make easy and cheap the remote transmission of strain gauge load cells analogue
signals to PLC, PC, recorders, remote indicators etc… until to a distance of 40m. TARE suppression (Switch B)
The possibility of internally connecting the load cells in parallel (max.4 of 350Ω or 8 of 700Ω) makes Switch 1 = 7% Switch 3 = 28%
system wiring easier by avoiding the use of junction boxes. It is ideal to be used in the most advanced Switch 2 = 15% Switch 4 = 28%
industrial weighing systems, processes control, dosing (silos and hoppers) and automation thanks to the
two versions of its case: hermetic case made of pressure die-cast aluminium (IP65 class) or plastic case FULL SCALE regulation (Switch D)
for mounting on a DIN guide (suitable for applications inside control panels) Input Output Output
The transmitter feeds the load cells, amplifies and filters the returned signal with high-precision and mV 10V 4÷20mA
long-term stability amplifiers; it is possible to internally perform all Zero and Full Scale calibrations 30 OFF OFF
through a dip switch for less accurate regulations and through a trimmer for precise regulations. 20 1 1
In order to soften vibrations or mechanical unsteadiness present in the plant, transmitter has an analog 15 2 2
filter which can be adjusted by the operator. 10 1,3 1,3
The TA4/2 transmitte offers two speed of response selectable by the user: the standard speed 5 1,4 1,4
(2.5Hz 16.5Hz) is obtained with J4 closed and acting on the F trimmer, the Fast speed (1KHz) is Insert the switch combining them until you
obtained with J4 open. get wanted result.
The analog output: 0÷20mA, 4÷20mA, ±5V, ±10V shall be indicated when order is placed. A = Fine Zero adjustment F = Analogue Filtrer adjustment
The immunity to the electomagnetic fields for the TAD/2 version is 3V/m. B = Switch for fixed Tare suppression J4 = Close = STD version (f=2.5÷16.5Hz)
On request, transmitter can be equipped with: C = Fine Full Scale adjustment J4 = Open = FAST version (f=1KHz)
Input signal : 1mV/V, 3 mV/V. D = Rough Full Scale adjustment
Case for a 35mm DIN bar.
ACCURACY CLASS TECHNICALZERO
≤±0.02% DATAadjustment ±70% CALIBRATION PROCEDURE
The transmitter is supplied already calibrated according to the specifications, but depending on the
LINEARITY ERROR ≤±0.02% ZERO fine adjustment ±10%
system which is being realized, it is necessary to perform ZERO and FULL SCALE regulations.
INPUT SIGNAL 2mV/V POWER SYPPLY 16÷26Vdc ZERO regulations is necessary to deduct the system fixed tare and reset the amplified output signal to
INPUT IMPEDANCE 10¹ºΩ MAX ABSORPTION 200mA the initial values.
Connectable LOAD CELLS 4 da 350Ω LOAD CELLS FEEDING 10Vdc ±4% This regulation can be performed by acting on B dip switch and on A trimmer.
ANALOG OUTPUT PROTECTION (EN60529) IP65 FULL SCALE regulations is performed by loading a sample weight on the system and by correcting the
CURRENT loading resistor max.470Ω CASE Alluminium amplified output, we recommend to perform this operation with a weight not lower than 50% of system
TENSION loading resistor min.3KΩ DIMENSIONS (HXLXP) 80x125x58 full scale.
STD response speed 2.5÷16.5Hz WEIGHT ~0.6kg This regulation can be performed by acting on D Dip Switch and C trimmer.
FAST response speed 1KHz EXTERNAL FUSE (F type) 500mA 250V Analogue FILTER regulation is performed depending on possible amplified signal instabilities due to
MAX WORKING TEMP. -10 ÷ +50°C weighing system vibrations, for a further filtering, please rotate clockwise the F trimmer.
STORAGE TEMP. -20 ÷ +70°C OPTIONS: When filter increases, the transmitter response decreases; in the Fast version (f=1kHz), the filter is
10°C TEMP. VARIATION: INPUT SIGNAL 1mV, 3mV disabled.
- On Zero ≤±0.01% ANALOG OUTPUT ±5V, ±10V
- On Full Scale ≤±0.01% 0÷20mA TRANSPORT
This is an instrument made of electric components, in case of transport pack it carefully, pay attention to
ZERO POTENTIOMETER 10KΩ DIN bar case DIN 35mm
both shocks and humidity.
FULL SCALE adjustment 5÷30mV DIMENSIONS (HXLXP) 82x144x42
FULL SCALE fine adjustment ±10% WEIGHT ~0.2kg
DELIVERY
Instrument is tested in any of its parts then configurated and calibrated.

INSTALLATION POWER ON
This indicator has been produced in conformity to the norms for the E.M.C. according to the Directive Connect the cables at terminals, feed the instrument.
89/336/CEE (and following changes). To respect them it is necessary to perform the electric POWER OFF
connections according to what indicated in this manual. Cut off the power.
POSITIONING MAINTENANCE
Instrument shall be positioned in the following way: Instrument does not require any periodic maintenance; occasionally remove contingent leavings of dirt
The TA4/2 model (IP65) must be fixed to a wall and not directly exposed to the atmospheric agents. with a air jet.
The TA4D/2 model must be fixed on a DIN guide inside a control panel that protects it from the DISPOSAL
atmospheric agents and screen it from the electromagnetic fields present in the industrial environment. Cut off the power. Disconnect cables.
DIMENSIONS (mm) Wrap instrument up either in a plastic package or in cardboard box.
Deliver the instrument to companies specialised in scrapping according to the laws in force.
TROUBLE SHOOTING
Instrument does not transmit the analogue signal, check power supply and internal fuse.

PURCHASE CODE
ETA4 Case Input Output Power Supply
/=Alluminium IX = 2mV O4 = 4-20mA D24
D = DIN O5 = ±5V
O11 = ±10V
O20 = 0-20mA

EPG7SET Pack with n° 3 metal fairleads.